Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 Mircom 2011 Printed in Canada Subject to change without prior not
System Components4EnclosuresFlush Trim RingsBatteriesRemote AnnunciatorsModel DescriptionBB-1024(add suffix “R” for red enclosure)Surface enclosure 24
FA-1000 Installation and Operation Manual5FA-1000 Fire Alarm Control Panel KitsFor any other sizes, etc., components are ordered separately.FA-1000 Ac
Mechanical Installation and Dimensions6Mechanical Installation and DimensionsInstall the enclosure as shown for the BB-1024 in Figure 1, or for the B
FA-1000 Installation and Operation Manual7Figure 2 BB-1072 Flush or Surface Enclosure Installation and Dimensions(SIDE VIEW)DOORBACKBOX7-9/16"BAC
Mechanical Installation and Dimensions8Main Chassis Installation1. Install the main chassis in the BB-1024 backbox as shown in Figure 3 below, using
FA-1000 Installation and Operation Manual9Main and Expander Chassis Installation1. Install the main and expander chassis into the BB-1072 enclosure, a
Module Mounting Locations10Module Mounting LocationsThe main chassis in a BB-1024 or BB-1072 enclosure comes pre-assembled with all power supply, main
FA-1000 Installation and Operation Manual11Figure 6 BB-1072 Expansion Chassis Mounting LocationsThe BB-1072 enclosure with an ECH-1048 expander chassi
12Module Mounting LocationsFigure 7 Circuit Adder Mounting DetailsMain ChassisMCC-1024-6 orMCC-1024-12Provision for PR-300 or UDACT-300AExpander Chass
FA-1000 Installation and Operation Manual13Module SettingsFigure 8 Main Fire Alarm ModuleJumpersJW1: Install jumper for Class A (Style D) operation of
Module Settings14Figure 9 Main Display Module (MCC-1024-6, MCC-1024-12)ConnectorsP1: Cable connects to P3 of main fire alarm module.P2: Connection to
FA-1000 Installation and Operation Manual15Figure 10 Main Display Module (MCC-1024-6S, MCC-1024-12S)On the MCC-1024-6S and MCC-1024-12S Chassis for th
Module Settings16Figure 12 Detection Adder Module (Model DM-1008A)JumpersJW1: Install jumper for Class A (Style D) operation of initiating circuits 1
FA-1000 Installation and Operation Manual17Figure 13 Signal Adder Module (Model SGM-1004A)JumpersJW1: Remove continuity jumper if there are any more a
Module Settings18Jumpers for the Bell Cut ModeJW2: Place jumper over pins 1 and 2 for the ability to remotely silence the bells on Zone 1.JW3: Place j
FA-1000 Installation and Operation Manual19Figure 15 Digital Communicator Module (Model UDACT-300A)Table 1 Cable Connectors and MiscellaneousThe foll
Module Settings20Jumper JW4 on the main fire alarm panel must be removed if a UDACT-300A is installed.Please see the UDACT-300A Installation and Opera
FA-1000 Installation and Operation Manual21Field WiringMain Fire Alarm Module Terminal ConnectionsWire devices to terminals as shown in Main Fire Ala
Field Wiring22Figure 18 Main Fire Alarm Module Terminal Connections (continued)Notes:• All power limited circuits must use type FPL, FPLR, or FPLP pow
FA-1000 Installation and Operation Manual23Detection Module (DM-1008A) Terminal ConnectionsWire devices to terminals as shown in Figure 19 below. For
FA-1000 Series Installation and Operation ManualiContentsIntroduction ...
Field Wiring24Signal Module (SGM-1004A) Terminal ConnectionsWire devices to terminals as shown in Figure 20 below. For more information see Wiring Tab
FA-1000 Installation and Operation Manual25Relay Module (RM-1008A) Terminal ConnectionsWire devices to terminals as shown in Figure 21 below. For more
Field Wiring26UDACT-300A Main Board Terminal ConnectionsWire the two telephone line devices to terminals as shown below in Figure 22 below. The UDACT-
FA-1000 Installation and Operation Manual27Polarity Reversal and City Tie Module (Model PR-300) Terminal ConnectionsWire as shown below in Figure 23
Field Wiring28Power Supply ConnectionsThe power supply is part of the main chassis. The ratings are outlined in the table below.For more information s
FA-1000 Installation and Operation Manual29Wiring Tables and InformationTable 4 Wiring Table for Initiating CircuitsTable 5 Wiring Table for Indicat
System Checkout30System CheckoutBefore Turning the Power On1. To prevent sparking, do not connect the batteries. Connect the batteries after powering
FA-1000 Installation and Operation Manual31TroubleshootingMessage DescriptionCircuit TroubleNormally when a circuit trouble occurs, its designated tro
Indicators, Controls, and Operation32Indicators, Controls, and OperationRefer to Figure 25 below for LED indicators, control buttons, and switches loc
FA-1000 Installation and Operation Manual33Common IndicatorsBuzzerThe buzzer is activated by any of the following:• Fire alarm : steady• Supervisory a
FA-1000 Series Installation and Operation ManualiiConfiguring Initiating and Indicating Circuits ...
Indicators, Controls, and Operation34configuration mode. If the panel is left in either mode for over an hour with no operator activity, this LED will
FA-1000 Installation and Operation Manual35the panel, but it is still in the first stage) cancels the timer and turns the Acknowledge LED on steady am
Indicators, Controls, and Operation36• The Circuit Status LED turns on steady amber when the corresponding circuit is in alarm. This LED will also fla
FA-1000 Installation and Operation Manual37Single Stage OperationIn a single stage system, all alarm inputs are treated in a similar manner. Alarm inp
Indicators, Controls, and Operation38• The buzzer sounds steadily • If signals have been silenced as a result of the silence button or the Auto signal
FA-1000 Installation and Operation Manual39Indicating (Signal) Circuits TypesEvacuation CodesSingle stage codesTwo-stage codes:Figure 26 Evacuation Co
System Configuration40System ConfigurationIntroduction to ConfigurationConfiguration of the FA-1000 Fire Alarm Control Panel is performed by a combina
FA-1000 Installation and Operation Manual41Table 6 Configuration DIP Switch FunctionsDIP Switch Position (1-8)Function NumberButton OperationsDescrip
System Configuration42Entering Configuration ModeThe system enters configuration mode whenever any of the configuration DIP switches 2 to 8 (switch 1
FA-1000 Installation and Operation Manual43Factory Default ConfigurationThe system as shipped from the factory is configured with no adder modules, an
FA-1000 Fire Alarm Control PaneliiiList of Figures and TablesFiguresFigure 1 BB-1024 Flush or Surface Enclosure Installation and Dimensions ...
System Configuration445. Set the Config DIP switch to 0100 0000 (resize system1). Wait five seconds.6. Press the yellow and red buttons together for f
FA-1000 Installation and Operation Manual45Configuring Initiating and Indicating CircuitsInitiating circuits (detection zones) and indicating circuits
System Configuration462. To configure circuits to be of that selected circuit type, turn on all of the desired circuit disconnect DIP switches (up pos
FA-1000 Installation and Operation Manual47With the factory default configuration, all outputs are configured to activate with any inputs configured a
Walk Test Operation48Display ConfigurationThe main and adder display modules on the front panel are automatically updated to display all circuits foun
FA-1000 Installation and Operation Manual49Appendix A: RA-1000 Remote Annunciator PanelsRA-1000 SeriesThe RA-1000 Series of remote annunciators are un
Appendix B: Device Compatibility List50Appendix B: Device Compatibility ListFA-1000 Series UL Listed Two-Wire Smoke DetectorsNotes: Whether mixing dif
FA-1000 Installation and Operation Manual51Hochiki continuedSLR-24/NS4-220 HD-3/HB-3 0.045mA 30SLR-24/HSC-220R HD-3/HB-3 0.045mA 30SLR-24H/NS6-220 HD-
Appendix B: Device Compatibility List52System Sensor continued2451 / B401B A - A 0.12 mA 252451 / B406B A - A 0.12 mA 252451 / DH400 A - N/A 0.12 mA 2
FA-1000 Installation and Operation Manual53FA-1000 Series UL Listed Compatible Four-Wire Smoke DetectorsSmoke Detector Make Model / BaseMaximum # of d
Appendix B: Device Compatibility List54FA-1000 Series UL Listed Compatible Signaling DevicesSystem Sensor - SpectrAlertWheelock continued Wheelock con
FA-1000 Installation and Operation Manual55FA-1000 Series ULC Listed Compatible Hardwire Smoke DetectorsNotes: Whether mixing different models of comp
Appendix B: Device Compatibility List56SIJ-24/NS6-220 30 1451-A/B401B 25SIJ-24/NS4-220 30 1451-A/B406B 25SIJ-24/HSC-220R 30 2451-A/B401B 25SLR-24/NS6-
FA-1000 Installation and Operation Manual57Appendix C: Module Specifications and FeaturesMain Fire Alarm Chassis (MCC-1024-6[SA]) Main Fire Alarm Chas
Appendix D: Power Supply and Battery Calculations58Appendix D: Power Supply and Battery CalculationsUse the form below to determine the required main
FA-1000 Installation and Operation Manual59Warranty and Warning InformationWarning Please Read Carefully Note to Installers This warning contains vita
Warranty and Warning Information60radio path or deliberate jamming or other inadvertent radio signal interference.System Users A user may not be able
FA-1000 Installation and Operation Manual61Component Failure Although every effort has been made to make this system as reliable as possible, the syst
Warranty and Warning Information62Warranty Procedure To obtain service under this warranty, please return the item(s) in question to the point of purc
FA-1000 Installation and Operation Manual1IntroductionAbout this ManualThis installation and operation manual provides information on installing the F
CANADA - Main Office25 Interchange WayVaughan, ON L4K 5W3Tel: (888) 660-4655 (905) 660-4655Fax: (905) 660-4113© Mircom 2011Printed in Canada
Introduction2Contact UsFor General Inquiries, Customer Service and Technical Support you can contact us Monday to Friday 8:00 A.M. to 5:00 P.M. E.S.T.
FA-1000 Installation and Operation Manual3System ComponentsChassisCircuit Adder ModulesAuxiliary ModelsModel DescriptionMCC-1024-6 (add suffix S for s