Mircom BPS-1100 Specifiche Pagina 1

Navigare online o scaricare Specifiche per Alimentatori Mircom BPS-1100. Mircom BPS-1100 Specifications Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 0
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113
Mircom 2011
Printed in Canada
Subject to change without prior notice
www.mircom.com
FA-1000 SERIES
Microprocessor-Based Fire Alarm Control Panel
LT-600 Rev. 16.1
November 2011
Installation and Operation Manual
For the latest compatability information visit www.mircom.com/deviceguide
Vedere la pagina 0
1 2 3 4 5 6 ... 71 72

Sommario

Pagina 1 - FA-1000 SERIES

Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113  Mircom 2011 Printed in Canada Subject to change without prior not

Pagina 2

System Components4EnclosuresFlush Trim RingsBatteriesRemote AnnunciatorsModel DescriptionBB-1024(add suffix “R” for red enclosure)Surface enclosure 24

Pagina 3 - Contents

FA-1000 Installation and Operation Manual5FA-1000 Fire Alarm Control Panel KitsFor any other sizes, etc., components are ordered separately.FA-1000 Ac

Pagina 4

Mechanical Installation and Dimensions6Mechanical Installation and DimensionsInstall the enclosure as shown for the BB-1024 in Figure 1, or for the B

Pagina 5 - List of Figures and Tables

FA-1000 Installation and Operation Manual7Figure 2 BB-1072 Flush or Surface Enclosure Installation and Dimensions(SIDE VIEW)DOORBACKBOX7-9/16"BAC

Pagina 6

Mechanical Installation and Dimensions8Main Chassis Installation1. Install the main chassis in the BB-1024 backbox as shown in Figure 3 below, using

Pagina 7 - Introduction

FA-1000 Installation and Operation Manual9Main and Expander Chassis Installation1. Install the main and expander chassis into the BB-1072 enclosure, a

Pagina 8 - Contact Us

Module Mounting Locations10Module Mounting LocationsThe main chassis in a BB-1024 or BB-1072 enclosure comes pre-assembled with all power supply, main

Pagina 9 - System Components

FA-1000 Installation and Operation Manual11Figure 6 BB-1072 Expansion Chassis Mounting LocationsThe BB-1072 enclosure with an ECH-1048 expander chassi

Pagina 10 - Remote Annunciators

12Module Mounting LocationsFigure 7 Circuit Adder Mounting DetailsMain ChassisMCC-1024-6 orMCC-1024-12Provision for PR-300 or UDACT-300AExpander Chass

Pagina 11 - FA-1000 Accessories

FA-1000 Installation and Operation Manual13Module SettingsFigure 8 Main Fire Alarm ModuleJumpersJW1: Install jumper for Class A (Style D) operation of

Pagina 13 - FLUSH TRIM

Module Settings14Figure 9 Main Display Module (MCC-1024-6, MCC-1024-12)ConnectorsP1: Cable connects to P3 of main fire alarm module.P2: Connection to

Pagina 14 - Main Chassis Installation

FA-1000 Installation and Operation Manual15Figure 10 Main Display Module (MCC-1024-6S, MCC-1024-12S)On the MCC-1024-6S and MCC-1024-12S Chassis for th

Pagina 15

Module Settings16Figure 12 Detection Adder Module (Model DM-1008A)JumpersJW1: Install jumper for Class A (Style D) operation of initiating circuits 1

Pagina 16 - Module Mounting Locations

FA-1000 Installation and Operation Manual17Figure 13 Signal Adder Module (Model SGM-1004A)JumpersJW1: Remove continuity jumper if there are any more a

Pagina 17

Module Settings18Jumpers for the Bell Cut ModeJW2: Place jumper over pins 1 and 2 for the ability to remotely silence the bells on Zone 1.JW3: Place j

Pagina 18

FA-1000 Installation and Operation Manual19Figure 15 Digital Communicator Module (Model UDACT-300A)Table 1 Cable Connectors and MiscellaneousThe foll

Pagina 19 - MAIN FIRE ALARM BOARD

Module Settings20Jumper JW4 on the main fire alarm panel must be removed if a UDACT-300A is installed.Please see the UDACT-300A Installation and Opera

Pagina 20 - MCC-1024-12 24

FA-1000 Installation and Operation Manual21Field WiringMain Fire Alarm Module Terminal ConnectionsWire devices to terminals as shown in Main Fire Ala

Pagina 21 - Display Module (Part

Field Wiring22Figure 18 Main Fire Alarm Module Terminal Connections (continued)Notes:• All power limited circuits must use type FPL, FPLR, or FPLP pow

Pagina 22 - FIELD WIRING TERMINALS

FA-1000 Installation and Operation Manual23Detection Module (DM-1008A) Terminal ConnectionsWire devices to terminals as shown in Figure 19 below. For

Pagina 23

FA-1000 Series Installation and Operation ManualiContentsIntroduction ...

Pagina 24

Field Wiring24Signal Module (SGM-1004A) Terminal ConnectionsWire devices to terminals as shown in Figure 20 below. For more information see Wiring Tab

Pagina 25 - ALARM CONTROL

FA-1000 Installation and Operation Manual25Relay Module (RM-1008A) Terminal ConnectionsWire devices to terminals as shown in Figure 21 below. For more

Pagina 26 - +

Field Wiring26UDACT-300A Main Board Terminal ConnectionsWire the two telephone line devices to terminals as shown below in Figure 22 below. The UDACT-

Pagina 27 - Field Wiring

FA-1000 Installation and Operation Manual27Polarity Reversal and City Tie Module (Model PR-300) Terminal ConnectionsWire as shown below in Figure 23

Pagina 28

Field Wiring28Power Supply ConnectionsThe power supply is part of the main chassis. The ratings are outlined in the table below.For more information s

Pagina 29 - (POWER LIMITED)

FA-1000 Installation and Operation Manual29Wiring Tables and InformationTable 4 Wiring Table for Initiating CircuitsTable 5 Wiring Table for Indicat

Pagina 30

System Checkout30System CheckoutBefore Turning the Power On1. To prevent sparking, do not connect the batteries. Connect the batteries after powering

Pagina 31

FA-1000 Installation and Operation Manual31TroubleshootingMessage DescriptionCircuit TroubleNormally when a circuit trouble occurs, its designated tro

Pagina 32

Indicators, Controls, and Operation32Indicators, Controls, and OperationRefer to Figure 25 below for LED indicators, control buttons, and switches loc

Pagina 33 - 3000 ohms

FA-1000 Installation and Operation Manual33Common IndicatorsBuzzerThe buzzer is activated by any of the following:• Fire alarm : steady• Supervisory a

Pagina 34 - Power Supply Connections

FA-1000 Series Installation and Operation ManualiiConfiguring Initiating and Indicating Circuits ...

Pagina 35 - Wiring Tables and Information

Indicators, Controls, and Operation34configuration mode. If the panel is left in either mode for over an hour with no operator activity, this LED will

Pagina 36 - System Checkout

FA-1000 Installation and Operation Manual35the panel, but it is still in the first stage) cancels the timer and turns the Acknowledge LED on steady am

Pagina 37 - Troubleshooting

Indicators, Controls, and Operation36• The Circuit Status LED turns on steady amber when the corresponding circuit is in alarm. This LED will also fla

Pagina 38 - 1814 18 18 18

FA-1000 Installation and Operation Manual37Single Stage OperationIn a single stage system, all alarm inputs are treated in a similar manner. Alarm inp

Pagina 39 - Common Indicators

Indicators, Controls, and Operation38• The buzzer sounds steadily • If signals have been silenced as a result of the silence button or the Auto signal

Pagina 40 - Common Controls

FA-1000 Installation and Operation Manual39Indicating (Signal) Circuits TypesEvacuation CodesSingle stage codesTwo-stage codes:Figure 26 Evacuation Co

Pagina 41 - Circuit Status Indicators

System Configuration40System ConfigurationIntroduction to ConfigurationConfiguration of the FA-1000 Fire Alarm Control Panel is performed by a combina

Pagina 42

FA-1000 Installation and Operation Manual41Table 6 Configuration DIP Switch FunctionsDIP Switch Position (1-8)Function NumberButton OperationsDescrip

Pagina 43 - Two Stage Operation

System Configuration42Entering Configuration ModeThe system enters configuration mode whenever any of the configuration DIP switches 2 to 8 (switch 1

Pagina 44 - Circuit Types

FA-1000 Installation and Operation Manual43Factory Default ConfigurationThe system as shipped from the factory is configured with no adder modules, an

Pagina 45 - Figure 26 Evacuation Codes

FA-1000 Fire Alarm Control PaneliiiList of Figures and TablesFiguresFigure 1 BB-1024 Flush or Surface Enclosure Installation and Dimensions ...

Pagina 46 - System Configuration

System Configuration445. Set the Config DIP switch to 0100 0000 (resize system1). Wait five seconds.6. Press the yellow and red buttons together for f

Pagina 47

FA-1000 Installation and Operation Manual45Configuring Initiating and Indicating CircuitsInitiating circuits (detection zones) and indicating circuits

Pagina 48 - Exiting Configuration Mode

System Configuration462. To configure circuits to be of that selected circuit type, turn on all of the desired circuit disconnect DIP switches (up pos

Pagina 49 - Factory Default Configuration

FA-1000 Installation and Operation Manual47With the factory default configuration, all outputs are configured to activate with any inputs configured a

Pagina 50 - Configuration Features

Walk Test Operation48Display ConfigurationThe main and adder display modules on the front panel are automatically updated to display all circuits foun

Pagina 51

FA-1000 Installation and Operation Manual49Appendix A: RA-1000 Remote Annunciator PanelsRA-1000 SeriesThe RA-1000 Series of remote annunciators are un

Pagina 52

Appendix B: Device Compatibility List50Appendix B: Device Compatibility ListFA-1000 Series UL Listed Two-Wire Smoke DetectorsNotes: Whether mixing dif

Pagina 53

FA-1000 Installation and Operation Manual51Hochiki continuedSLR-24/NS4-220 HD-3/HB-3 0.045mA 30SLR-24/HSC-220R HD-3/HB-3 0.045mA 30SLR-24H/NS6-220 HD-

Pagina 54 - Walk Test Operation

Appendix B: Device Compatibility List52System Sensor continued2451 / B401B A - A 0.12 mA 252451 / B406B A - A 0.12 mA 252451 / DH400 A - N/A 0.12 mA 2

Pagina 55 - RA-1000 Series

FA-1000 Installation and Operation Manual53FA-1000 Series UL Listed Compatible Four-Wire Smoke DetectorsSmoke Detector Make Model / BaseMaximum # of d

Pagina 57

Appendix B: Device Compatibility List54FA-1000 Series UL Listed Compatible Signaling DevicesSystem Sensor - SpectrAlertWheelock continued Wheelock con

Pagina 58

FA-1000 Installation and Operation Manual55FA-1000 Series ULC Listed Compatible Hardwire Smoke DetectorsNotes: Whether mixing different models of comp

Pagina 59

Appendix B: Device Compatibility List56SIJ-24/NS6-220 30 1451-A/B401B 25SIJ-24/NS4-220 30 1451-A/B406B 25SIJ-24/HSC-220R 30 2451-A/B401B 25SLR-24/NS6-

Pagina 60

FA-1000 Installation and Operation Manual57Appendix C: Module Specifications and FeaturesMain Fire Alarm Chassis (MCC-1024-6[SA]) Main Fire Alarm Chas

Pagina 61

Appendix D: Power Supply and Battery Calculations58Appendix D: Power Supply and Battery CalculationsUse the form below to determine the required main

Pagina 62

FA-1000 Installation and Operation Manual59Warranty and Warning InformationWarning Please Read Carefully Note to Installers This warning contains vita

Pagina 63

Warranty and Warning Information60radio path or deliberate jamming or other inadvertent radio signal interference.System Users A user may not be able

Pagina 64

FA-1000 Installation and Operation Manual61Component Failure Although every effort has been made to make this system as reliable as possible, the syst

Pagina 65

Warranty and Warning Information62Warranty Procedure To obtain service under this warranty, please return the item(s) in question to the point of purc

Pagina 67

FA-1000 Installation and Operation Manual1IntroductionAbout this ManualThis installation and operation manual provides information on installing the F

Pagina 70

CANADA - Main Office25 Interchange WayVaughan, ON L4K 5W3Tel: (888) 660-4655 (905) 660-4655Fax: (905) 660-4113© Mircom 2011Printed in Canada

Pagina 71

Introduction2Contact UsFor General Inquiries, Customer Service and Technical Support you can contact us Monday to Friday 8:00 A.M. to 5:00 P.M. E.S.T.

Pagina 72 - Printed in Canada

FA-1000 Installation and Operation Manual3System ComponentsChassisCircuit Adder ModulesAuxiliary ModelsModel DescriptionMCC-1024-6 (add suffix S for s

Commenti su questo manuale

Nessun commento